The drives support the static standard PDO mapping of CANopen specification DSP402 plus extensions as indicated in the column "Comment". Note: Objects 6074 (torque demand value) and 6077 (torque actual value) display currents rather than torque, object 6071 (target torque) is not supported.
Transmit PDO:
TPDO No. | Object Index | Object Name | Bytes | Comment |
1 |
6041 60FD:1 |
statusword digital input signals |
2 4 |
digital input signals is extension to DSP402 |
2 |
6041 6061 |
statusword modes of operation display |
2 1 |
|
3 |
6041 6064 |
statusword position actual value |
2 4 |
|
4 |
6041 606C 606B |
statusword velocity actual value velocity demand value |
2 4 2 |
velocity demand value is extension to DSP402, data length must be shortened to 2bytes |
5 |
6041 6077 6074 |
statusword torque actual value torque demand value |
2 2 2 |
torque demand value is extension to DSP402 |
Receive PDO:
RPDO No. | Object Index | Object Name | Bytes | Comment |
1 |
6040 60FE:1 |
controlword digital output signals |
2 4 |
digital ouput signals is extension to DSP402 |
2 |
6040 6060 |
controlword modes of operation |
2 1 |
|
3 |
6040 607A |
controlword target position |
2 4 |
|
4 |
6040 60FF |
controlword target velocity |
2 4 |
|
5 |
6040 6071 |
controlword target torque |
2 2 |
|